Series PLT |
Ultrasonic Level Transmitter Continuous, Noncontact, 4 to 20 mA Output |
Series UL Ultrasonic Level Transmitters provide continuous noncontact sensing for level control of liquids or slurries. The sensor emits an ultrasonic pulse which is reflected back to the sensor at the liquid/air interface. The distance traveled by the pulse is calculated and converted into a 4-20 mA output signal. Internal microprocessor performs self diagnostics to indicate possible operating problems such as out-of-range or loss of echo. Failsafe feature can be set to deliver a 3 or 21 mA output in the event the echo is lost.
Model Number
|
Description
|
UL100
UL200
|
15 ft (4.5 m) range with 2" PVC flange
35 ft (10.5 m) range with 3" PVC flange
|
PHYSICAL DATA
|
Accuracy:
|
|
±0.3% of span
|
|
Repeatability:
|
|
±0.125" (±3 mm) typical
|
|
Supply Voltage:
|
|
115±10% VAC, 50/60 Hz, 5 VA
|
|
Output:
|
|
4-20 mA into 600W, isolated
|
|
Blind Zone:
|
|
(UL 100) 12" (cm), (UL 200) 18" (cm)
|
|
Beam Angle:
|
|
Conicle 12°
|
|
Sensor Pressure Rating:
|
|
150 psig maximum
|
|
Temperature Compensation:
|
|
-200 to 180°F (-30 to 82°C)
|
|
Temperature Range:
|
|
Sensor: -20 to 180°F (-30 to 82°C), Electronics: -10 to 160°F (-23 to 71°C)
|
|
Sensor Material:
|
|
CPVC
|
|
Control Box Enclosure:
|
|
Polycarbonate, NEMA 4X
|
|
Mounting:
|
|
(UL 100) 2" PBC 150# flange, (UL 200) 3" PBC 150# flange
|
APPLICATIONS
Monitor and control levels of water, wastewater, oils, chemicals, acids, caustics, viscous liquids, and slurries.
|