Series 860 |
Line Voltage Thermostats Built-in thermometer, heavy duty construction |
  |
Heavy duty and reliable, Model 860 Line Voltage thermostat is designed for direct control of motors operating HVAC equipment in industrial environments. Hermetically sealed mercury switch resists dust, dirt, grease and moisture. Cadmium plated steel and brass mechanism resists corrosion. Set point is easily adjustable via knurled knob located on the side of the unit. Knob may be removed to prevent tampering. Contacts rated up to 17A available on special order.
PHYSICAL DATA
|
Temperature Limits:
|
|
-10 to 140°F
|
|
Electrical Rating:
|
|
See Chart
|
|
Deadband:
|
|
Approximately 2-4°F
|
|
Wiring Connections:
|
|
Standard - screw type terminals, explosion-proof pigtail leads for connection inside junction box
|
|
Conduit Opening:
|
|
½" on explosion-proof model. Standard unit mounts on standard wall switch box
|
|
Set Point Adjustment:
|
|
Removable knob at side of unit
|
|
Housing:
|
|
Standard units have plastic housing. Explosion-proof units have cast aluminum housing containing electrically live parts. Thermostat mechanism is located in front of housing for better sensitivity; mechanism is covered by plastic cover
|
|
Actuation:
|
|
Liquid filled brass bellows
|
|
Installation:
|
|
Vertical
|
|
Weight:
|
|
Standard unit - 1.5 lbs. Explosion-proof unit - 4.5 lbs.
|
Model Number SPDT1
|
Model Number SPDT2
|
Operating
Range, °F
|
Housing
|
860-153-61
860153-62
860-153-63
860-153-64
860-153-65
860EH-153-61
860EH-153-62
860EH-153-63
860EH-153-64
860EH-153-65
|
860-2-61
860-2-62
860-2-63
860-2-64
860-2-65
860EH-2-61
860EH-2-62
860EH-2-63
860EH-2-64
860EH-2-65
|
25-60
38-70
56-80
65-90
80-110
25-60
38-70
56-80
65-90
80-110
|
Indoor
Indoor
Indoor
Indoor
Indoor
Explosion Proof
Explosion Proof
Explosion Proof
Explosion Proof
Explosion Proof
|
1 Three terminals: common, normally open, normally closed, 4A @ 120 V, 2A @ 240V, (AC or DC). 1/8 HP @ 120/240 VAC 1Ø (Not U.L. or C.S.A. listed)
2 Two terminals: common, normally closed (opens on temperature rise). 10A @ 120V, 5A @ 240V, AC or DC. ¾ HP @ 120/240 VAC 1Ø ¼ HP @ 120/240 VDC. Normally open (instead of standard normally closed contact) is available on special order.
|
SUGGESTED SPECIFICATIONS
Thermostats shall have heavy duty contacts suitable for 120/240V operation. Contacts shall be hermetically sealed and mercury wetted. Units shall include integral thermometer. Enclosures shall be (indoor)(explosion0proof) type. Units shall be bellows actuated and shall have removable set point adjust knob. Units shall be Mercoid Model 860.
|