Calibration-Free, 2-Wire Design, Duct or Wall Mount
CE



Monitor and control relative humidity and temperature in building energy management systems with the Series HT Humidity/Temperature Transmitter. Designed for demanding HVAC/EMCS applications, the Series HT provides ±3% RH accuracy and ±1% stability per year. Routine calibration is not required with the fully interchangeable sensor. Two-wire connections allows easy instillation directly into air ducts or within a controlled area.

PHYSICAL DATA
Relative Humidity Range:   10 to 90% RH
Temperature Range:   Duct mount: 14 to 140°F (-10 to 60°C), wall mount: 23 to 131°F (-5 to 55°C).
Accuracy:   ±3% RH @ 25°C, ±0.3°C @ 25°C.
Stability:   ±2% RH over 2 years.
RH Temperature Dependence:   <±1.5% RH from 14 to 140°F (-10 to 60°C).
Temperature Dependence:   0.01°C/°C.
Temperature Sensor:   Pt 1000W RTD.
Response Time:   15 seconds.
Output Signal:   4 to 20 mA.
Supply Voltage:   10 to 28 VDC.
Current Consumption:   4 mA minimum.
Operating Humidity Range:   Duct mount: 0 to 100% RH, wall mount: 0 to 90% RH.
Operating Temperature Range:   Duct mount: 14 to 140°F (-10 to 60°C), wall mount: 23 to 131°F (-5 to 55°C).
Storage Temperature:   -40 to 140° F (-40 to 60° C).
Conduit Connection:   1/2" NPT.
Mounting Connection:   3/4" NPT.
Housing Material:   ABS plastic.
Enclosure:   NEMA 4X/IP65
Weight:   0.6 lb (0.3 kg).

Model Number
Description
HT00*
HT01
TD10*
TD11
Humidity Transmitter, wall mount
Humidity Transmitter, duct mount
Humidity/Temp Transmitter, wall mount
Humidity/Temp Transmitter, duct mount
*wall mount not shown


ACCESSORY
No. HT5, Replacement sensor




Back