Model PD690
Precision Digital's Model PD690 is a high performance, easy to use, industrial-grade microprocessor digital process meter. It accepts all the standard process signals: 4-20 mA, 1-5 V, 0-5 V and 0-10 V and displays these signals in engineering units on a 4-1/2 digit display. The display includes an extra zero which may be used to handle numbers up to 199,990. Universal Process Meter
Features   Specifications   Order Info
Features
- Easy Single Button Scaling with Lockout Feature
- 4-20 mA, 0-5 V, or 0-10 V Field Selectable Inputs
- 24 V Transmitter Power Supply Standard
- Stand Alone Scaling
- Steady, Accurate Display to +/- 199,990
- 11 Point Linearization
- Square Root Extraction
- 4-1/2 Digit + Extra Zero
- NEMA 4X Front Panel
- 2 or 4 Relay + 4-20 mA Output Options
- Isolated 18-36 VDC Powered Option
- Green Display Available
- Easy Setup Instructions on Meter
Top   Features   Specifications   Order Info
Ordering Information
Model: Description 115 VAC    *PD690-3-N No Options    *PD690-3-14 2 Relays *PD690-3-15 4-20 mA Output *PD690-3-16 2 Relays + 4-20 mA Output *PD690-3-17 4 Relays *PD690-3-18 4 Relays + 4-20 mA Output 230 VAC PD690-4-N No Options PD690-4-14 2 Relays PD690-4-15 4-20 mA Output PD690-4-16 2 Relays + 4-20 mA Output PD690-4-17 4 Relays PD690-4-18 4 Relays + 4-20 mA Output 18-36 VDC PD690-2-N No Options PD690-2-14 2 Relays PD690-2-15 4-20 mA Output PD690-2-16 2 Relays + 4-20 mA Output PD690-2-17 4 Relays PD690-2-18 4 Relays + 4-20 mA Output * Quick Shipment Item, shipped within two working days Most other products shipped within one week, call for best shipping date. Note: A -G may be added in the part number to call out meters
with a green display ex. PD690-3G-14; Options: Model: Description PD174 2 Relay Option (-14 in P/N) PD175 4-20 mA Output Option (-15 in P/N) PD176 2 Relays + 4-20 mA Output (-16 in P/N) PD177 4 Relays Output Option (-17 in P/N) PD178 4 Relays + 4-20 mA Output (-18 in P/N) PDX-6901 Snubber Top   Features   Specifications   Order Info
Specifications
Basic Meter
- INPUTS: Field selectable, 4-20 mA, 1-5 V, 0-5 V, 0-10 V.
- DISPLAY: Bright, Large, 0.56" (14.2mm) high efficiency red or green LED. 4-1/2 digits + extra zero; +/- 19999(0), (0) may be switched on to display 199,990.
- FRONT PANEL: NEMA 4X, panel gasket provided.
- CALIBRATION: May be calibrated using internal calibration (I-CAL) or by applying an external calibration signal (E-CAL).
- CALIBRATION RANGE: 4 mA (1V) input may be set to display anywhere in range of meter. 20 mA (5V) may be set anywhere above or below 4 mA input. Non-volatile Memory: All programming values are stored in non-volatile memory for ten years if power is lost.
- LOCKOUT: Jumper 3 at rear of instrument restricts modification of calibration values.
- LOOP POWER: (AC powered units only) Isolated 24VDC at 20 mA regulated. Noise less than 10 mV p-p. Max loop resistance of 1200 ohms. Available for either signal input or 4-20 mA output option, but not both.
- HOLD READING: Connect terminals HLD and COM.
- ACCURACY:.05% of calibrated span.
- INPUT IMPEDANCE: Voltage ranges, greater than 300 Kohms; Current range, 100 ohms.
- POWER: AC power: 115 VAC +/- 10%, 50/60 Hz, 10VA. 230 VAC +/- 10%, 50/60 Hz, 10VA. DC power: 18-36 VDC, 6 watts max.
- ISOLATION: AC power: 1500 VAC; DC power: 500 VDC.
- ENVIRONMENTAL: Operating temperature range: 0 to 65¡C. Storage temperature range: -40 to 85ûC. Relative Humidity: 0 to 90% non-condensing.
- ENCLOSURE: 1/8 DIN, high impact plastic, UL 94V-0.
- CONNECTIONS: Removable screw terminal block (provided).
- ALARM POINTS: 4, any combination of high or low alarms.
- ALARM STATUS INDICATION: Front panel LED.
- ALARM DEADBAND: 0-100%, User Selectable.
- UL FILE NUMBER: E160849; 508 Industrial Control Equipment.
Relays
- RATING: 2 or 4 relays; 2 Amp SPDT (form C). The contacts are rated 2 Amp @ 30 VDC or 2 Amp @ 250 VAC resistive load; 1/14 HP @ 125 / 250 VAC for NC contacts and 1/10 HP @ 125 / 250 VAC for NO contacts, inductive load.
- RESET: User Select. 1. Automatically when the input passes the reset point. 2. Automatically + manually (via user supplied switch or front panel ACK button).
- FAILSAFE OPERATION: The relay coils are energized in the non-alarm condition. In the case of a power failure, the relays will go to the alarm state. May be disabled with internal jumper.
- AUTO INITIALIZATION: When power is applied to the meter, the relays will always reflect the state of the input to the meter.
- DEADBAND: 0-100%, User Selectable.
Isolated 4-20 mA Transmitter Output
- CALIBRATION RANGE: Anywhere in range of meter, 501 count minimum span.
- OUTPUT LOOP RESISTANCE:
Loop Resistance Power Supply Min Max 24 VDC 10 ohm 600 ohm 36 VDC (external) 600 ohm 1000 ohm
- ISOLATION: 500 VDC or peak AC, input-to-output or input/output-to-power line.
- EXTERNAL LOOP POWER SUPPLY: 35 V max.
Top   Features   Specifications   Order Info